General information
With multidata you have acquired one of the
most up-to-date, modern heat calculators cur-
rently available on the market.
Expressive symbols in the display and easy
menu navigation make readout simple. It can be
operated with one single button. The setting of
the data loggers (depending on the type of de-
vice) is being done via the software GMM.
The calculator is equipped with a long-life battery
made for operation during the initial verication
validity period (5 years) including a reserve of at
least another year. With a second battery you will
reach 11 years.
Initial verification
multidata is produced and tested in compliance
with the new European measuring instruments
directive (MID). According to this directive, de-
vices do no longer carry an initial verication
stamp, but rather the year of the device’s decla-
ration of conformity (recognizable on the front of
the device, for example: M09). The MID controls
the use of heat meters up to the moment they
are placed on the market resp. their rst putting
into use. After this, the national regulations for
devices subject to legal verication apply within
the EU.
Technical data multidata
Temperature range
°C 1 - 150
Temperaturdifferenz k 3 - 120
Display Multifunctional LCD, 8-digit, oating
Display unit
MWh, kWh, GJ, MJ
Interface ow sensor
Models with contact pulsers or active pulser
(no Namur or Opto),
passive max. 1Hz / active max. 100 Hz
Temperature sensor connection
PT500, optional PT100, PT1000
Max. cable length 2-wire
12,5 m (PT500), 2,5 m (PT100), 20 m (PT1000)
Max. cable length 4-wire
20 m
Interfaces
optical, optionally ZR-Bus (RS-485), M-Bus, RS-232,
remote readout outputs
Ambient temperature
°C 5 - 55
Power supply
Battery 3.6 V Lithium,
optionally mains power supply 230V/24V
Battery lifetime
6 years, optionally 11 years
Protection class IP 54 / IP 65, acc. to DIN 40050
Mechanical/electro-magnetic class
M1/E1
Accuracy class according to EN1434
Measuring cycle dynamic
40s/30s/10s